Voltagedrop "is the voltage drop, and the voltage drop of XLPE cable is due to the resistance of the conductor. Because of this, regardless of the material used for the conductor (copper/aluminum), it will cause a certain voltage loss in the circuit, and when this loss (voltage drop) is not greater than 5% of its own voltage, it generally does not have any consequences on the power drive of the circuit.
For example, for a 380V line, if the voltage drops to 19V, which means the circuit voltage is not lower than 361V, there will not be significant problems. Of course, we hope that this pressure drop will be as small as possible. Because pressure itself is an electrical loss, although it is inevitable, we always hope that the pressure drop is within an acceptable range.
1. Calculate the line current I
I= P/1.732×U×cosθ
Among them: P-power (kW); U-voltage (kV); Cos θ - power factor (0.8-0.85)
2. Calculate the line resistance R
R=ρ×L/S
Among them: ρ - conductor resistivity (copper core cable ρ=0.01740, aluminum conductor ρ=0.0283); L - Line length (meters); The nominal cross-section of S-cable
3. Calculate line voltage drop (simplest and most practical):
ΔU=I×R
Calculation formula for line voltage drop: △ U=2 * I * R, I - line current; L - Line length
Limit the cross-sectional area of the wire according to the heating conditions at close range (safe current carrying capacity);
On the basis of safe current carrying capacity at long distances, the wire cross-section should be selected according to the voltage loss conditions to ensure that the working voltage at the load point is within the qualified range;
The allowable current density to ensure the continuous operation of the wire for a long time is called the safe current carrying capacity. The general rule is to select 5-8A/mm ² copper wire; Aluminum wire should be selected at 3-5 A/mm ². The safe current carrying capacity should also be determined based on comprehensive factors such as the maximum temperature, cooling conditions, and laying conditions of the core wire usage environment of the wire.
In general, with short distance, small cross-sectional area, good heat dissipation, and low temperature, the conductivity of the wire is stronger, and the upper limit of safe current carrying is selected; Due to long distance, large cross-sectional area, poor heat dissipation, high temperature, poor natural environment, etc., the conductivity of the wire is weaker, and the lower limit for safe current carrying is selected;
The ambient temperature is 40 degree ; The temperature of the wire is 70-90 degree ; Cable arrangement: single core, S=2D; power factor cos θ=0.8; The allowable percentage of voltage reduction at the end is Less than or equal to 5%.
Among them: Vd - voltage drop, Vd=KxIxLxV0 (v); I - Working current or calculated current (A); L - Line length (m); V0- In table voltage (V/A.m); K: Three phase four wire K=√ 3 single-phase K=1
Allowable voltage drop during single-phase operation: Vd=220Vx5%=11V
Allowable voltage drop during three-phase operation: Vd=380Vx5%=19V